April 2019
> A recent intervention on a site in southern Brazil shows the consistency of the values of tensile forces obtained from the vibration analysis tests with the values deduced from the calculation of earth pressure on the retaining wall (photo attached).
Earth pressure calculation From the dynamic stiffness Column 1 Column 2 13,54t 12,88t 13,83t
23,35t 26,40t 22,79t
The interpretation of the non-destructive testing is improved when it relies on static tests performed in conjunction with dynamic tests. The tests on the anchoring rods are adapted to semi-infinite massifs.